LIGHTNING STRIKE COUNTER FOR WIND TURBINES

EOLOS K15FO

HIGH BANDWIDTH LIGHTNING STRIKE COUNTER WITH OPTICAL FIBRE OUTPUT FOR WIND TURBINES.

DL EOLOS K15FO lightning strike counters register and account local strikes impacting on wind turbine blades. The compact design and robust construction, combined with a high current impulse bandwidth, makes this product a perfect fit for monitoring the most common types of lightning strike impacts registered in wind turbine blades and elevated structures.


 

FEATURES

Characteristics

DL EOLOS K15FO lightning strike counters also provide an optical fibre output for remote event notifications to SCADA, PLC and other modules inside the wind turbine. The output optical fibre event notification signals generated by the DL EOLOS K15FO counter can be received and decoded by the DL EOLOS FO-RCVR-3CH three channels optical fibre receiver.

The DL EOLOS K15FO detects the current impulse produced by the lightning strike in the lightning protection system down conductor. Registered lightning strikes are reported as events in the optical fibre output and, at the same time, accounted in one mechanical counter.

The high bandwidth magnetic sensor used in the DL EOLOS K15FO counter ensures a contact-free installation and a maintenance free operation.

These counters harvest all necessary energy from the lightning strike current impulse without any need for batteries, external power sources or moving parts.

  • Accounting of up to 999 events.
  • Permanent visibility of accounted events count.
  • High detection sensitivity for a wide impulse current bandwidth, including typical wind turbine impacts as described by standard IEC 61.400-24.
  • Direct attachment to wind turbine blades with adhesive.
  • No need for external power or batteries.
  • Contactless current impulse measurement sensor without ohmic contact with the down conductor.
Download data sheet
PDF icon EOLOS K15FO

TECHNICAL DATA

Technical specifications
NameValue
Current wave front from 8µs to 2000µs
Current range from ±180A to ±200kA
Current impulse immunity (10/350μs) ±200kA
Counting range Up to 999 events (rolls down to 000)
Temperature range from -20ºC to 60ºC
Protection grade IP 65
Dimensions 139x44x68 mm
Weight 770g
Downconductor diameter 22 mm
Output connector SMA for 1mm POF optical fibre
Output data format Proprietary
Event notification delay 680μs (typical)
 
 
INSTALLATION

instalacion contador de rayos para aerogeneradores

It is recommended to install one DL EOLOS K15FO counter per wind turbine blade in conjunction with one DL EOLOS FO-RCVR-3CH optical fibre receiver.


CERTIFICATIONS


IEC 62.305, UNE 21.186 and NFC 17-102 standards indicate the need to install lightning strike counters as part of lightning protection systems. Lightning protection systems must be inspected and checked after the occurrence of any impact on the structure. DL EOLOS K15FO counters assist the maintenance planning staff in reducing the wind turbine down time as they allow accurate knowledge of impacted blades.

DL EOLOS K15FO counters have been designed to comply with IEC 62.561-6 standard requirements, with the exception of the minimum current threshold. The counter's current threshold has been optimized for detecting lightning impacts as described by IEC 61.400-24 standard.

DL EOLOS K15FO counters have been tested in combination with the DL EOLOS FO-RCVR-3CH receiver for current impulse immunity at LABELEC, Laboratorio de Ensayos Electrotécnicos (ENAC accreditation number 307/LE681).