FLD 5, 5098 60 0, 5098600, chống sét tín hiệu đo lường 5V, tín hiệu điều khiển 5V, tín hiệu thông tin viễn thông 5V, Long Triết
MCR protection for two-core systems
Medium and fine protection for two-core systems 5 V
Surge protection for use in measurement and control technology
• Medium and fine protection
• Standard design for single core systems
• Two-stage protection circuit
• With installation-friendly, screwless connection terminals
• In space-saving 17.5 mm grid
• With inductive decoupling in the longitudinal branch
Application: Universal use on any 35 mm hat profile rail in every commercially available distributorhousing.
FLD 5 | |||
Article number | 5098 60 0 | ||
Maximum continuous voltage AC | UC | V | 5 |
Maximum continuous voltage DC | UC | V | 8 |
Category | Type 1+2+3 / D1+C2+C1 | ||
Lightning protection zone LPZ | 0→3 | ||
Number of poles | 2 | ||
Rated current | IL | A | 1 |
Series inductivity per wire | 120 μH ± 20 % | ||
Impulse durability wire-wire | C1: 1 kV / 0.5 kA (8/20 μs) | ||
Impulse durability wire-earth | C2: 10 kV / 5 kA (8/20μs) | ||
Total discharge current (8/20) | kA | 10 kA | |
Total discharge current (10/350) | kA | D1: 3 kA | |
Protection level wire-wire | V | <15 V | |
Protection level wire-earth | V | <600 V | |
Temperature range | ϑ | °C | -40 - +80 °C |
Installation type | DIN rail 35 mm | ||
Connection system | Terminal | ||
Division unit TE (17.5 mm) | 1 | ||
Protection rating | IP20 | ||
Connection cross-section, flexible | mm² | 0.14 - 0.75 mm² | |
Connection cross-section, multi-wire | mm² | 0.14 - 0.75 mm² | |
Connection cross-section rigid | mm² | 0.14 - 0.75 mm² | |
Earthing via: | Terminal | ||
Testing standard | IEC 61643-21 |