Kim thu sét chủ động hiện đại phát xạ sớm Ingesco PDC-E60, PDC.60, PDC60, 102007, phân phối nhập khẩu kim thu sét Ingesco PDC
Download Catalogue tài liệu tổng kim thu sét Ingesco Tây Ban Nha
Kim thu sét chủ động chịu được cường độ dòng sét cực đại lên đến 200KA (dòng sét xảy ra ở VN đo được tối thiểu trên 01 lần sét đánh là 90KA), bán kính bảo vệ 120m
INGESCO® PDC.E ELECTRONIC LIGHTNING ROD WITH ESE (EARLY STREAMER EMISSION)
It is suitable for external lightning protection of all types of structures and open areas
- High level protection.
- 100% of efficacy in discharge capture.
- It doesn’t need external power supply.
- Operation guaranteed in any atmospheric condition.
- An external structure made from stainless steel AISI 316 L.
DESCRIPTION
PDC.E lightning rod with electronic ESE system offer the most effective and safe protection before lightning. They have been designed to reduce the time of the electro atmospheric discharge, in order to increase their capacity for lightning capture. When a storm cloud is near to produce a downward electrical discharge (lightning), an increase in the electric field takes place. The electronic ESE system accumulates this electric potential and afterwards releases it as high voltage impulses that ionize the air particles around device. This process produces an upward streamer emission that attracts and captures lightning.
The capture terminal of INGESCO® PDC.E, fits the following technical specifications:
- It has an electronic ESE (Early Streamer Emission) system.
- A capacitive generator of an upward emission.
- A capacitive circuit to store electric charges.
- An insulation system made with resin (certified for high voltage devices protection).
- An external structure made from stainless steel AISI 316 L.
Its effective operation in any atmospheric condition and environment is thus guaranteed.
LEVEL OF PROTECTION
Protection radii calculated according to: Norm UNE 21.186:2011 & NFC 17.102:2011 (These radii of protection have been calculated according to a height difference of 20 m between the tip of the lightning rod and the considered horizontal plane).
INGESCO PDC.E LIGHTNING ROD mod. | PDC.E 15 | PDC.E 30 | PDC.E 45 | PDC.E 60 |
---|---|---|---|---|
Reference | 102004 | 102005 | 102006 | 102007 |
Δt | 15 µs | 30 µs | 45 µs | 60 µs |
LEVEL I | 35 m | 50 m | 65 m | 80 m |
LEVEL II | 43 m | 59 m | 74 m | 89 m |
LEVEL III | 54 m | 70 m | 86 m | 102 m |
LEVEL IV | 63 m | 81 m | 97 m | 113 m |
CERTIFICATIONS
INGESCO® PDC.E, fits the requirements contained in norms:
- NP4426:2013
- IEC 62.305
- UNE 21.186:2011
- IEC 62.561/1
- NFC 17.102:2011
- IEC 62.561/3
- Evaluation test of the upward leader initiation time emitted by the lightning rods with ESE system (Annex C UNE 21.186:2011 and NFC 17.102:2011), at the LABELEC High Voltage Laboratory.
- Mechanical test (traction and flexion until breakage).
- Product certificate issued by the Bureau Veritas Certification entity.
- Lightning protection test components according IEC 62.561/1, in the LABELEC High Voltage Laboratory.
- Certificate of insulation in rainy conditions issued by the LABELEC High Voltage Laboratory.
INSTALLATION
The capture terminal of INGESCO® PDC.E should follow the prescriptions of the norms UNE 21.186:2011, NFC17-102:2011, NP4426:2013 y IEC62.305, and should take into account the following:
- The point of the lightning rod should be situated, at least 2 m. above the highest building to be protected.
- For its installation on a mast, the corresponding head-mast adapter is needed for the lightning rod.
- The cabling of the covers should be protected against surges and connect to ground the metallic structures present within the safety zone.
- The lightning rod should be connected to a grounding point by way of two or various conducting cables which will go down, whenever possible, the exterior of the construction with the shortest and straight possible trajectory.
- The hearth termination systems, whose resistance are not surpass 10 ohms, should guarantee the most rapid possible dispersion of the lightning current discharge.
TECHNICAL DATA
Mod. | Ref. | Mat. | H (mm) | ØD1 (mm) | ØD2 (mm) | M1 | Weight (g) |
---|---|---|---|---|---|---|---|
PDC.E15 | 102004 | Inox | 412 | 16 | 83 | M 20 | 3775 |
PDC.E30 | 102005 | Inox | 412 | 16 | 83 | M 20 | 3770 |
PDC.E45 | 102006 | Inox | 412 | 16 | 83 | M 20 | 3765 |
PDC.E60 | 102007 | Inox | 412 | 16 | 83 | M 20 | 3760 |