ÜSM-A-4, USM-A-4, chống sét, chống sét nguồn điện cấp 3, chống sét nguồn điện, OBO-Bettermann, Long Triết
Fine power protection, fixed installation
Fine power protection with holder for GB2 and GB3 mounting boxes
Surge protection module type 3 to DIN EN 61643-11 for 230 V power grids.
• With acoustic defect signal
• With low construction height and Y circuit
• Holder (separating retainer function) for installation in GB2 and GB3 mounting boxes
Application: Universally applicable for all installation systems.
| ÜSM-A-4 | |||
| Article number | 5092 47 2 | ||
| Nominal voltage | Un | V | 230 |
| Max. continuous operating voltage | UC | V | 255 |
| SPD to EN 61643-11 | Type 3 | ||
| SPD to IEC 61643-11 | Class III | ||
| Lightning protection zone LPZ | 2→3 | ||
| Nominal discharge current (8/20) | In | kA | 3 |
| Maximum discharge current (8/20 μs) | Imax | kA | 6 |
| Protection level (L-N) | Up | kA | <1,3 |
| Protection level (N-PE) | Up | kA | <1,5 |
| Maximum back-up fuse | A | 16 | |
| Response time | tA | ns | <25 |
| Temperature range | ϑ | °C | -15 - +60 |