VF60ACDC, 5097 62 3, 5097623, chống sét, chống sét nguồn điện cấp 3, chống sét nguồn điện 60V AC DC, chống sét lan truyền, OBO
Fine power protection, series installation
Protection for 2-pole for power supply, 60 V
Surge protective device / fine protection Type 3 to EN 61643-11
• Suitable for DC and AC voltage system
• With visual function display
• With installation-friendly, screwless connection terminals
• In a space-saving 17.5 mm grid
• Y circuit
Application: Universal use on 35 mm DIN rail in every normal commercially available distributorhousing.
| VF60ACDC | |||
| Article number | 5097 62 3 | ||
| U max AC | Uc AC | V | 80 |
| U max DC | Uc DC | V | 110 |
| SPD to EN 61643-11 | Type 3 | ||
| SPD to IEC 61643-11 | Class III | ||
| Lightning protection zone LPZ | 2→3 | ||
| Nominal discharge current (8/20) | In | kA | 0,7 |
| Rated current | IL | A | 20 |
| Protection level wire-wire | Up | V | <280 |
| Protection level wire-earth | Up | V | <1200 |
| Response time | tA | ns | <25 |
| Temperature range | ϑ | °C | -40 - +80 |
| Protection rating | IP 20 | ||
| Division unit TE (17.5 mm) | 1 | ||
| Connection cross-section rigid | 0.14 - 2.5 mm² | ||
| Connection cross-section, multi-wire | 0.14 - 2.5 mm² | ||
| Connection cross-section, flexible | 0.14 - 2.5 mm² | ||